ANALISIS KELAYAKAN ISOLASI TRANSFORMATOR #4 70 /20 KV 20 MVA DENGAN METODE INSPEKSI LEVEL 3 DI GARDU INDUK 70 kV TULUNGAGUNG

Authors

  • Latifah Rahmawati Universitas Kahuripan Kediri
  • Riska Nur Wakidah Universitas Kahuripan Kediri
  • Aulidina Dwi Nur Andriyanti Universitas Kahuripan Kediri
  • Dwi Sari Ida Aflaha Universitas Kahuripan Kediri

DOI:

https://doi.org/10.61722/jssr.v4i6.13358

Keywords:

polarization index, transformer insulation, tangent delta, breakdown voltage

Abstract

The reliability of power transformers is influenced by insulation quality, which requires evaluation through maintenance testing. This study aimed to determine the results of polarization index, tangent delta, and breakdown voltage (BDV) tests and assess the insulation suitability of Transformer #4, rated at 20 MVA with a voltage of 70/20 kV, at the 70 kV Tulungagung Substation. A quantitative method with a descriptive analytical approach was applied using data from the two-year maintenance inspection conducted on April 23, 2024. The results showed that the polarization index ranged from 1.26 to 1.89, while tangent delta values ranged from 0.12% to 0.34%. The average BDV of the bottom main tank oil was 71.6 kV/2.5 mm, whereas the oil in the On-Load Tap Changer (OLTC) reached 66.1 kV/2.5 mm. The test results met the reference limits specified in SKDIR No. 0520-2.K/DIR/2014. Based on the three testing parameters, the transformer insulation met the applicable maintenance standards, and the transformer was considered suitable for operation.

References

G. Arinsyah Prima, A. Zuriman, and A. Anggun, “Analisa Tahanan Isolasi pada Transformator Daya 150/30 kV Gardu Induk Padang Luar PT PLN (Persero) Bukittinggi,” 2023.

U. Muhammadiyah and S. Oleh, “Analisa Tahanan Isolasi pada Transformator Tenaga di Gardu Induk Wonogiri,” 2017.

N. Fidianti, “Skripsi Teknik Elektro,” 2013.

V. Alfionita, “Analisa Tahanan Isolasi Transformator Tenaga di Gardu Induk Sepatan dengan Metode Indeks Polarisasi, Tangen Delta dan Break Down Voltage,” Universitas Mercu Buana, Jakarta, 2020.

A. R. Hidayat, “Analysis of Power Transformer Insulation: A Case Study in 150 kV Bantul Substation,” J. Electr. Technol. UMY, vol. 3, no. 2, 2019.

A. G. Cahyani, “Analisa Kinerja PMT dan PMS pada GI Pasir 150 kV dengan Metode Thermography,” 2023.

P. T. P. L. N. (Persero), “Buku Petunjuk Pengoperasian Peralatan Gardu Induk 70 kV Tulungagung,” PT PLN (Persero), Tulungagung, 2024.

Downloads

Published

2026-11-11